Distributors Stock

Need more information?

Contact us to request pricing, availability and customization options

Contact Us

Specifications

Current Ratings
(Amps)
T/R/PP/PR
DC Resistance
T/R/PP/PR
50/60Hz Impedance
CR/CPP/CPR
DC Resistance
.100 175 181 274
.500 6.34 6.83 9.77
1.00 1.63 1.69 2.31
2.00 .400 .425 .465
3.00 .175 .188 .261
4.00 .103 .106 .156
5.00 .076 .078 .091
7.50 .038 .039 .053
10.0 .026 .028 .023
12.5 .020 .021 .020
15.0 .013 .014 .010
20.0 .010 .011 .008
25.0     .004
30.0     .003
DCR and Impedance is measured after 1 hour at 100% rated current using the Voltmeter-Ammeter Method.

 

Delay Pulse Tolerance
1, 2, 61, 62 *9 Times Rated Current
3, 4, 61F, 62F *13 Times Rated Current
*Units above 15 amps are derated to 8 and 12 times rated current