Introducing SGX 750V, 400A Contactors, utilizing our ceramic to metal weld technology – the ultimate solution for a variety of applications, including residential energy storage systems (ESS), DC fast charging, electric forklifts, AGVs, and other industrial vehicles. The SGX series offers an excellent performance-to-cost advantage over competitors, making them excellent drop-in replacements for other brands.
Hermetically seal rated to 175°C – Reduced risk of fire or meltdown in over current conditions.
Backfilled with gas (primarily hydrogen) to effectively inhibit oxidation, resulting in low and stable contact resistance.
Contact us to request pricing, availability and customization options
Contact UsContact Arrangement | 1 Form A |
Contact Resistance | ≤ 0.5 mΩ @ 200A |
Rated Load Current | 400A (@ 200 mm2 wire) |
Rated Switching Voltage | 450 VDC / 750 VDC |
Rated Switching Power | 180 kW @ 450 VDC 350 kW @ 750 VDC |
Min. Applicable Load | 6 VDC, 1A |
Max. Switching Voltage | 1000 VDC |
Max. Switching Power | 300 kW (750 VDC) |
Max. Breaking Current | 2000A (750 VDC), 1 cycle |
Specifications | Data | |
Dielectric Strength | Between Open Contacts | 3000 VAC, 1 min |
Between Coil & Contacts | 3000 VAC, 1 min | |
Insulation Resistance | 1000 MΩ at 1000 VDC | |
Operate Time (at nomi. volt.) | ≤ 50ms | |
Release Time (at nomi. volt.) | ≤ 10ms | |
Vibration Resistance (sine) | 10 Hz - 500 Hz, 49 m/s2 | |
Shock Resistance | Functional Open: 196 m/s2 | |
Functional Close: 588 m/s2 | ||
Destructive: 490 m/s2 | ||
Ambient Temperature | -40°C - 85°C | |
Humidity | 5% RH - 85% RH | |
Termination | M6 female screw | |
Mounting | M5 screw | |
Unit Weight | Approx. 760 g | |
Outline Dimensions | Refer to drawings |
Nominal Voltage (VDC) | Pick-up Voltage (VDC) | Drop-out Voltage (VDC) | Coil Power (W) |
12 | ≤ 9 | ≥ 1 | ∼6.0 @ 23°C |
24 | ≤ 18 | ≥ 2 |
Specifications | Data | |
Electrical Endurance | Switch on: 7.5 x 104 cycles (22.5 VDC, 140 A, C = 1100 μF) Switch off: 7.5x104 cycles (450 VDC, 5 A) | |
Switch off: 2.5 x 104 cycles (450 VDC, 10 A) Switch off: 3.0 x 103 cycles (450 VDC, 200 A) | ||
Switch off: 1.0 x 103 cycles (750 VDC, 400 A) | ||
Switch off: 100 cycles (750 VDC, 2000 A) | ||
Switch off: 1 cycle (450 VDC, 2000 A) | ||
Short Circuit Current | 500 VDC, 10000 A t ≤ 5ms, 1 cycle (no smoke, no fire) | |
Current Endurance | 400 A, cont. | |
500 A, 8 min | ||
1350 A, 2 min | ||
200 A, 25 s | ||
3000 A, 20 s | ||
Mechanical Endurance | 2 x 105 cycles, on-off ratio: 0.6 s : 5.4 s |