Features

  • Pure sine wave – Power your TVs, computers and other sensitive electronics without worry. The pure sine wave inverter and power factor corrected charger provide clean, reliable inverter power with low total harmonic distortion (THD) of less than 5%.
  • Choices – The MS-PAE Series comes in 24 and 48 volt configurations, allowing you to choose the model that is right for you.
  • Versatile mounting – Mount the MS-PAE Series on a shelf or wall.
  • Lightweight – The lightweight aluminum base and cover also provides noise reduction and corrosion resistance.
  • Multiple ports – The MS-PAE Series provides multiple ports, including an RS485 communication port for network expansion, and a remote port.
  • Accessible design – The extra large AC access cover with terminal screw block and 360° DC connection terminals with covers make this inverter more accessible when it needs to be.
  • Convenient switches – The MS-PAE Series comes with an on/off inverter-mounted switch with an easy-to-read LED indicator.

Specifications

Input battery voltage range 18 - 34 VDC
AC output voltage accuracy 120/240 VAC split phase (± 5%)
Output frequency and accuracy 60 Hz ± 0.1 Hz
Total Harmonic Distortion (THD) < 5%
1 msec surge current (amps AC) Line-Neutral: 120, Line-Line: 70
100 msec surge current (amps AC) Line-Neutral: 72, Line-Line: 40
5 sec surge power (real watts) 5800
30 sec surge power (real watts) 5200
5 min surge power (real watts) 4800
30 min surge power (real watts) 4500
Continuous power output at 25° C 4000 VA (L-L)
Maximum continuous input current 266ADC
Inverter efficiency (peak) 93%
AC Relay Transfer time (minimum) 16 msecs
Power Consumption - searching <6 watts
Power Consumption - inverting (no load) 27 watts
Output Waveform Pure Sine Wave
Continuous output at 25° C 105 ADC
Charger efficiency 85%
Power factor > .95
Input current at rated output (AC amps) 15 AAC per leg
at 120/240 VAC split phase
Transfer relay capability 2 legs at 30A per leg transfer standard on all models
Five stage charging capability Bulk, Absorb, Float, Equalize (requires remote), and Battery Saver™
Battery temperature compensation Yes, 15 ft Battery Temp Sensor standard
Internal cooling 0 to 120 cfm variable speed drive using dual 92mm brushless DC fans
Overcurrent protection Yes, with two overlapping circuits
Overtemperature protection Yes on transformer, MOSFETS, and battery
Corrosion protection Yes, PCB’s conformal coated, powder coated chassis/top, and stainless steel fasteners
Listings ETL Listed to ANSI / UL1741 and CSA STD C22.2 No.107.1-01
Warranty Three years parts and labor (five years when installed on MMP or MP system)