The Sensata ResonixTM RGD sensor provides accurate leak detection for HVAC systems leveraging A2L refrigerants - delivering a solution with a 15+ year lifetime. This factory-set sensor designed specifically for UL60335-2-40 delivers fast response times and low power consumption, requires no re-zeroing or field calibration, and is targeted for R32, R454A, R454B, R454C, and R455 refrigerants.
Contact us to request pricing, availability and customization options
Contact UsLearn more with the Sensata Resonix RGD Sensor promo video.
Materials | Housing: 33% PPA Resin Cable: PVC |
Dimensions | 50 x 80 x 18 mm |
Vibrations | 10 Hz to 31.5 Hz with 1.0 mm total excursion 31.5 Hz to 150 Hz with 2G acceleration peak |
Weight (Approx.) | 50 g |
Output | RS485 Modbus RTU |
Supply Voltage | 3.3 to 5 VDC |
Current consumption | < 40 mA |
Target Gases | Certified for R32, R454A, R454B, R454 Refrigerants. R455 and R1234yf Available |
LFL Range | 0 - 100% |
Response Time | T28 = 2.5 seconds, T60 = 5 seconds |
Warm Up Time | < 5 seconds |
Accuracy | +/- 2.5% of LFL |
Working Temperature | -40°C to +85°C constant, +85°C to +105°C intermittent |
Storage Temperature | -40°C to +105°C |
Working Humidity | 0 to 100% RH (condensing) |
Working Pressure | 70 to 120 kPa |
Protection (EN 60529) | IP54 |
Fault Detection | Sensor Out of Range |
Calibration | Factory calibration, no field calibration required |
Compensation | Temperature and humidity |
Lifetime | > 15 years |
Conformity | UL 60335-2-40 ed.4 Annex LL, UL 60335-2-89 ed.2 Annex 101.DP |