Distributors Stock

Need more information?

Contact us to request pricing, availability and customization options

Contact Us

Features

  • Hydraulic-magnetic technology
  • Up to 3 poles, 0.5 amps to 63 amps rated current at MAX 415 VAC
  • TUV and CCC approved, CE certified
  • UL1077 recognized (supplementary protector)
  • MAX 10,000 AIC short circuit amperage rating
  • Available in various current and time delays
  • Precise trip characteristics
  • Trip indication with mid-trip position
  • Auxiliary and alarm switches are available
  • NFPA130, EN45545-2, BSS7239 fire and smoke

Specifications

PolesHertzMax (Volts)Rated (Amps)Short Circuit (Amps)Agency
1,2N/A80 DC0.50 - 63.010,000CCC (GB 14048.2) & TUV (IEC 60947-2) & CRCC
1,2N/A110 DC0.50 - 63.010,000
2N/A220 DC0.50 - 50.06,000
1,250/60/400240 AC0.50 - 63.06,000
1,250/60/400240 AC0.50 - 63.03,000
250/60/400415 AC0.50 - 25.06,000
2,350/60/400415 AC0.50 - 50.03,000
1,2,3N/A110 DC0.50 - 63.010,000UL 1077 & CSA*
1,2,350/60240 AC0.50 - 63.06,000

*Model ICLR / ICLHE are supplementary protectors listed to CSA Std. C22.2 No. 235

% Overload - Trip Time in Seconds
Delay100%125%150%200%400%600%800%1000%
41No tripMay trip0.5 - 80.15 - 1.90.02 - 40.006 - 0.250.004 - 0.10.004 - 0.05
42No tripMay trip5 - 702.2 - 250.4 - 50.012 - 20.006 - 0.20.006 - 0.015
43No tripMay trip35 - 35012 - 1201.5 - 200.015 - 2.20.01 - 0.220.01 - 0.1
49No tripMay trip0.100 Max0.050 Max0.020 Max0.020 Max0.020 Max0.020 Max
51No trip0.5 - 6.50.3 - 30.1 - 1.20.031 - 0.50.011 - 2.50.004 - 0.10.004 - 0.08
52No trip2 - 601.8 - 301 - 100.15 - 20.015 - 10.008 - 0.50.006 - 0.1
53No trip80 - 70040 - 40015 - 1502 - 200.015 - 90.015 - 0.550.012 - 2
59No trip0.120 Max0.100 Max0.050 Max0.022 Max0.017 Max0.017 Max0.017 Max
61No trip0.7 - 120.35 - 70.130 - 10.030 - 10.015 - 0.30.01 - 0.150.008 - 0.1
62No trip10 - 1206 - 602 - 200.2 - 30.015 - 0.80.015 - 0.80.01 - 0.25
63No trip50 - 70030 - 40010 - 1501.5 - 200.013 - 0.850.013 - 0.850.013 - 0.5
69No trip0.120 Max0.100 Max0.050 Max0.022 Max0.017 Max0.017 Max0.017 Max
71No trip0.44 - 100.3 - 70.1 - 30.03 - 10.012 - 0.30.004 - 0.150.004 - 1
72No trip1.8 - 1001.7 - 6001 - 200.15 - 30.015 - 20.008 - 0.790.006 - 0.28
73No trip50 - 60030 - 40010 - 1501.8 - 200.015 - 100.015 - 0.880.011 - 0.5
79No trip0.100 Max0.100 Max0.050 Max0.022 Max0.016 Max0.015 Max0.015 Max

 

DelayPulse Tolerance
61, 62, 63, 71, 72, 7310X approx. Rated Current
61F, 62F, 63F, 71F, 72F, 73F12X approx. Rated Current

 

Typical Breaker Resistance / Impedance
Current Rating (Amps)DC Resistance (Ohms)50/60 Hz Impedance (Ohms)400 Hz Impedance (Ohms)
51, 52, 53, 5961, 62, 63, 64, 65, 66, 6941, 42, 43, 49
0.20045.828.571.94
11.381.102.85
20.3710.290.76
50.0550.0510.12
100.0170.0160.032
200.0060.0060.010
300.0030.0040.006
500.00190.00180.0019
630.001570.00134-

 

Agency CertificationRated AmperageMaximum VoltageShort Circuit Amperage
UL 4892 to 20 Amps240 VAC, 50 / 60 Hz5000
TUV (EN60947-2)2 to 20 Amps240 VAC, 50 / 60 Hz5000