Features

  • Switch and trip indication
  • Standard 35mm rail mounting
  • Precise overload protection
  • Integrated auxiliary signals (active/passive)
  • Manual priority
  • Remote/on-site/maintenance mode
  • Wide range of operating voltages
  • Anti-interference control signal
  • Failsafe function
  • Power failure memory function
  • Self-recovery function
  • Status indication
  • Anti-static/surge/pulse

Specifications

Rated operating voltage Voltage range
110 VDC 77 VDC - 137.5 VDC
Breaker Poles 1 - 3 poles
Life Cycle 10,000 times, 3 per minute
Voltage 80 VDC, 110 VDC, 240 VAC, 415 VAC
Current 63 A max
Vibrations and shocks MIL-STD-202, IEC61373
Venting Sealed, non-sealed
Fire and smoke certifications NFPA130, EN45545-2
Agency approval UL1077, GB14048.2 TUV60947-2, IEC 60077:2017, EN 50155:2017
Switching time < 1 second
Operating temperature -20 to + 60°C
Control signal 110 VDC (350-650) ms square-wave pulse
Operating current (peak) 110 VDC 0.25A 1S 25W
Static current < 30 mA
Poles Hertz Max (Volts) Rated (Amps) Short Circuits (Amps) Agency
1, 2 N/A 80 DC 0.50 - 63.0 10,000 CCC (GB 14048.2) & TUV (IEC 60947-2) & CRCC
1, 2 N/A 110 DC 0.50 - 63.0 10,000
2 N/A 220 DC 0.50 - 50.0 6,000
1, 2 50/60/400 240 AC 0.50 - 63.0 6,000
1, 2 50/60/400 240 AC 0.50 - 63.0 3,000
2 50/60/400 415 AC 0.50 - 25.0 6,000
3 50/60/400 415 AC 0.50 - 50.0 3,000
1, 2, 3 N/A 110 DC 0.50 - 63.0 10,000 UL 1077 & CSA*
1, 2, 3 50/60 240 AC 0.50 - 63.0 6,000

* Model ICLR/ICLHR are supplementary protectors listed to CSA Std. C22.2 No. 235