Sensata Technologies provides circuit-on-demand from a pre-wired power bus. The Airpax™ modular distribution system utilizes "plug 'n play" capabilities to simplify the design of your power bus system. The module design simplifies the line/load interface, saving both money and valuable time by eliminating the need for the shutdown when expanding the equipment.
Additionally, this flexible interface allows for adjacent circuits to be fused or protected, while parallel alarm conductors simplify signal wiring. By specifying the number of protected circuits, the MDS2 can be designed to meet your application requirements. Sensata, known for our high-quality products and outstanding customer service, once again sets the standard in innovative and precision technology with our new MDS2.
Contact us to request pricing, availability and customization options
Contact UsApplication | For use with Airpax™ IEL, IML, LEL and LML type circuit protectors and breakers using 5/16 inch diameter bullet terminals |
Electrical Ratings | 100 amperes max. load bus rating per position max. common bus of the 8 position system is 600 amperes. Voltage rating is 125 vdc |
Flammability | All modular distribution system parts have UL 94 V0 flammability rating |
Insulation Resistance | Min. 100 megohms @ 500 vdc |
High-Low Temperature Operation | -40ºC to +85ºC |
Dielectric Strength | 2000 VDC |
Recommended Torque Specifications | Load bus 1/4-20 UNC: 40 to 45 inch pounds Load bus m6 x 1.0: 4 to 5 Nm Mechanical support must be provided to terminals while applying torque. |
Auxiliary Switch Wire | 18 awg (ul 1213) |
Ampacity | Line bus 600 amperes: 800 amps/sq. inch Load bus 100 amperes: 1250 amps/sq. inch |