Part #DRA1-CX240A5R
Contact us to request pricing, availability and customization options
Contact UsOperating Voltage [VAC] | 12 - 280 |
Transient Overvoltage [Vpk] | 600 |
Maximum Load Current [Arms] | 5 |
Minimum Load Current [Arms] | 0.06 |
Maximum Off-Sate Leakage Current @ Rated Voltage [mArms] | 0.1 |
Maximum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] | 500 |
Maximum 1 Cycle Surge Current (50/60 Hz) [Apk] | 239 / 250 |
Maximum I2t for Fusing (50/60 Hz, ½ Cycle) [A2 Sec] | 285 / 260 |
Maximum On-State Voltage Drop @ Rated Current [Vpk] | 1.4 |
Control Voltage Range | 90 - 140 Vrms |
Must Turn-On Voltage | 90 Vrms |
Must Turn-Off Voltage | 10 Vrms |
Typical Input Current | 10 mA |
Nominal Input Impedance | 14.1K Ohms |
Maximum Turn-On Time [msec] | 10 |
Maximum Turn-Off Time [msec] | 40 |
Dielectric Strength, Input/Output (50/60 Hz) | 4000 Vrms |
Maximum Insulation Resistance (@ 500 VDC) | 109 Ohm |
Maximum Capacitance, Input/Output | 10 pF |
Ambient Operating Temperature Range | -30 to 80°C |
Ambient Storage Temperature | -30 to 125°C |
Weight (Typical) | 0.063 lb (28.6 g) |
Encapsulation | Thermally Conductive Epoxy |