Distributors Stock

Need more information?

Contact us to request pricing, availability and customization options

Contact Us

Features

  • Robust High Voltage/High Power load break bi-directional DC contactor
  • Designed for high voltage Power conversion equipment OEM’s: Photovoltaic/Battery inverters, battery pack designers, DC combiner boxes and other HVDC industrial drive systems
  • Excellent isolation performance: 10kv withstand between open contacts for critical safety applications
  • Mechanically linked SPDT auxiliary contacts for critical safety applications
  • Reliable indication of the main contacts in the closed position
  • Hermetically Sealed - Exceeds IP67-69 specifications. No exposed arcing to open air environments
  • Designed to meet UL1604 for hazardous locations

Product Applications

  • Energy Storage System
  • DC fast charging
  • Photovoltaic controls

Specifications

Specifications Units Data

Main Contact Arrangement

Auxiliary Contact Arrangement

Form X

Form C

SPST-NO

SPDT

Mechanical Life cycles 300,000
Auxiliary Contact Load Life (3A @ 24 Vdc)* cycles 300,000

Max @ rated carry current Contact Resistance*

Typical @ rated carry current Contact Resistance*

m ohms

m ohms

0.3

0.15

Max Close Operate time, 25°C (includes bounce)

Typical Close Operate time, 25°C (includes bounce)

ms

ms

85

70

Release time (includes arc time at max, break current) ms 70
Insulation Resistance* M ohms 100
Dielectric at sea level (leakage < 1mA) V 5375
Impulse Withstand Voltage (per IEC 61000-4-5) kV 10
Voltage Withstand (open contacts, 1 min. < 1mA leakage) kV 10
Shock, 1/2 Sine, 11 ms G peak 10
Vibration, Sinusoidal (500-2000 Hz peak) G 10

Operating ambient Temperature Range

Storage ambient Temperature Range

°C

°C

-55 to +85

-70 to +125

Weight, typical kg 3 (6.6 lb)
Environment seal - Exceeds IP67 & IP69K
Salt fog - MIL-STD-810

*View more specifications and exceptions in the datasheet.

Make & Break Cycles
400 A @ 1500 VDC 3750*
500 A @ 1200 VDC 3750*
600 A @ 1000 VDC 3750*

*View more specifications and exceptions in the datasheet.

Make Only Iterations
8000 A @ 24 VDC 7
6000 A @ 1000 VDC 1
1000 A @ 24 VDC 7000

 

Break Only Iterations
1500 A @ 1250 VDC 7
2700 A @ 1000 VDC 1
5000 A @ 400 VDC 2

 

Closed Contacts Iterations
8000 A / 50ms 10
10,000 A / 2ms 3

 

Coil P/N Designation B C F
Coil Voltage, Nominal (VDC) 12 24 48
Coil Type Dual Dual Dual
Coil Voltage, Max (V) 14 30 64
Pick-up Voltage, Max (V) 8 16 40
Drop-out Voltage (V) Coming soon 11 Coming soon
Coil Current (A)* 0.75 0.37 0.19
Coil Power (W)* 9 9 9
Internal Coil Suppression TVS TVS TVS
Coil Back EMF (V) 55 55 125
Transients, Max (V) (13 ms) 55 55 130

*View more specifications and exceptions in the datasheet.